MPPT Solar Charge algorithm maximises conversion efficiancy up to 99.5%. Battery Charging function configurable to suit local environment preferences and reliabilty requirements in multiple priority modes:
Inverter DC-AC module uses SPWM to produce Pure Sine wave output suitable for residential and commercial / scientific applications.
AC Inverter Module can be configured to run on:
Control and Monitoring : Large 4.2 inch inbuilt display with realtime opertional data. Control and Monitor the system with PC Software or Android App.
Electrical Specification:
UPower Series / Model Number | 3 KVA/ (UP3000-M3322) |
---|---|
System Battery Voltage (and Range) | 24 V DC (21.6~32VDC) |
Output Power (15min.) | 3000W (Continous 2400W) |
Max. Surge Power | 6000W |
Inverter Output Voltage / Frequency | 220VAC±3%, 230VAC (-7%~+3%) / 50Hz/60Hz |
Inverter Output Wave | Pure Sine Wave |
Distortion THD | ≤3% (12V or 24V resistive load) |
AC Utility Input Voltage | 160VAC~280VAC(Working voltage range), 170VAC~270VAC(Utility starting voltage range) |
Max. Utility Charge Current | 30A |
Max. PV Open Circuit Voltage | 92V |
Max. PV Input Power | 780W |
Max. PV Charging Current | 30A |
Battery Type | Lead Acid (AGM / Gel / Sealed / Flooded) / User Custom Battery Voltage Settings (e.g. Lithium*, etc.) |
Battery (Equalization/Boost/Float) Voltage | 29.2 V / 28.8 V / 27.6 V |
Temperature Compensation Coefficient | -3mV/℃, 2V (Default) |
MPPT Tracking Efficiency | upto 99.5% |
PC Connectivity Option | RS485 Interface |
Inbuilt Relay Interface | Can drive resistive loads 125VAC /1A, 30VDC/1A. Relay triggered by battery voltage sensing parameters DON / DOF (See manual). |
Environment Specification:
Operating Temperature Range | -20°C ~ +50°C |
Relative Humidity | ≤95%, N.C |
Enclosure | IP30 |
Physical Specs:
Parameter | |||
---|---|---|---|
Dimension | 444×300×126mm | ||
Mounting Dimension | 230mm | ||
Mounting Hole Size | Φ8mm | ||
Weight | 9.2kg |
Full Protection Functions:
PV Over Current, PV Short Circuit, Night Reverse charging, Battery & PV reverse polarity, Battery over discharge, Battery over heat, Battery over voltage, Load Short Circuit, Load Overload, and Device overheating. Note: To comply with IEC62109 requirement, connector for battery temp sensor is now located inside the unit.
CE, RoHS.
Box Contains: